GUARDIAN TEMPERING VALVE, 6 GALLON CAPACITY MODEL : G3600LF
Mixing valve, thermostatic, for eyewash assembly, blends hot and cold water to deliver warm (tepid) water, use with G1814BC eyewash unit, sold by the each
- Downloads


Mixing valve, thermostatic, for eyewash assembly, blends hot and cold water to deliver warm (tepid) water, use with G1814BC eyewash unit, sold by the each

Application: Self-contained eyewash/drench hose unit is ideal for use in low traffic areas, and where a continuous supply of potable water is unavailable for plumbed units. Unit is heated and insulated to endure low or freezing temperatures over long periods of time. Unit is fully freeze-resistant and tempered, for both indoor and outdoor environments. 15 gallon pressurized unit is ideal for floor placement near any hazard, and delivers approximately 10 usable gallons (37.9 liters) of water for 15 minutes, thus complying with the provisions of ANSI Z358.1-2014 for eyewashes.
Tank And Jacket: 15 gallon stainless steel pressurized tank with 10 gallons (37.9 liters) usable capacity. Tank has built-in carrying handles, Schrader air intake valve, pressure gauge and pressure relief valve. Highly visible orange Diener Nylon insulation jacket is waterproof and mildew resistant.
Heating Element: Silicone drum heater is attached to the tank with a spring latch. Water temperature inside of the tank is regulated by an onboard thermostat set to 65°F. Total amp draw is 3.33A and delivers 400W of power, which allows the unit to operate to temperatures as low as -20°F.
Ground Fault Plug: Unit comes standard with a 15A Ground Fault Circuit Interrupter (GFCI) with manual reset connected to a 9 foot long cord.
Eyewash Spray Head Assembly: Two GS-Plus™ spray heads. Each head has a “flip top” dust cover, internal flow control and filter.
Eyewash Valve: 1/2” IPS chrome plated brass three-way self-draining stay-open ball valve with stainless steel flag handle. Pressure regulator controls eyewash flow to 0.65 GPM for 15 minutes.
Drench Hose Unit: Auxiliary hand-held drench hose for rinsing eyes, face or body. Unit has single GS-Plus™ spray-type outlet head, self-closing valve with squeeze handle, and 6 ft. reinforced PVC hose.
Operation: To operate unit, fill with clean potable water and add bacteriostatic additive (supplied with unit). Additive protects against growth of bacteria, fungus, algae and acanthamoeba. After filling with water, pressurize unit to 80 PSI. If necessary, adjust pressure regulator to achieve maximum flow for 15 minutes. Unit should be inspected regularly and water should be changed at least once every six months. Filling instructions included.
Weight: 41.5 lbs. empty, 124.8 lbs. filled.
Sign: ANSI compliant identification sign permanently affixed to insulated jacket.
Quality Assurance: Unit is fully assembled, pressurized and water tested at the factory. Unit is depressurized and emptied prior to shipping. Some assembly required in the field.

Application: Test emergency equipment for proper operation. Includes Tyvek® chute and pail to contain tested water flow and prevent spillage.
Note: ANSI Z358.1 requires weekly activation of emergency equipment for a period long enough to verify operation and ensure flushing fluid is available.
Contents: 48″ telescopic aluminum pole, 11-1/2″ diameter Tyvek® test chute, 5 gallon plastic pail, and eyewash tester.

Application: Recessed emergency shower with ceiling mounted recessed shower head. Recessed shower conserves valuable floor space, while eliminating the clutter and obstruction created by conventional shower equipment. Unit can be installed in either a corridor or a lab room, close to where accidents might occur.
ADA Compliance: When installed at recommended mounting heights, unit complies with ADA requirements for accessibility by handicapped persons.
Shower Head: 10” diameter stainless steel with 20 GPM flow control and flange for flush mounting in ceiling.
Valve: 1″ IPS brass stay-open ball valve with stainless steel “panic bar.” Pulling bar down activates shower; shower remains in operation until bar is returned to original closed position. Furnished with stainless steel access panel and 1″ IPS unions for valve.
Mounting: 16 gauge stainless steel cabinet with flange featuring 3/8” return for recessed mounting in wall.
Supply: 1″ NPT female inlet.
Sign: ANSI-compliant identification sign.
U.S. Patent 5,768,721
Note: ANSI Z358.1-2014 specifies that shower heads be installed no more than 96″ above the finished floor. This unit should therefore not be installed in ceilings over 8 feet. For higher ceiling heights, we recommend either the GBF1670 or GBF1672 showers.

Guardian EyeSafe™ Eyewash, 2 Heads, Faucet Mounting, Pull Knob Operation, Aluminum Eye Wash Handle, Forged Brass Valve, Chrome Plated Brass Fitting, 55/64-27 FNPT Inlet Fitting, 1 in Diameter Head, Specifications Met: ANSI Z358.1-2014


Application: Recessed barrier-free eye/face wash and shower safety station with ceiling mounted exposed shower head and drain pan. Stainless steel cover provides attractive appearance and protects unit when not in use. When activated, cover serves as pan to collect waste water and return it into unit for drainage. Rather than connecting to building drainage system, unit has 1” IPS stainless steel drain on front of unit for waste water. Front drain provides for less costly installation while facilitating regular testing of unit.
ADA Compliance: When installed at recommended mounting heights, unit complies with ADA requirements for accessibility by handicapped persons.
Shower Head: 10″ diameter stainless steel with 20 GPM flow control. Furnished with vertical supply pipe and ceiling escutcheon for mounting shower head at desired height below finished ceiling.
Shower Valve: 1″ IPS brass stay-open ball valve with stainless steel “panic bar” actuator.
Cover/Drain Pan: 16 gauge stainless steel combination cover and drain pan. Grasping “panic bar” handle and opening cover pulls spray head assembly down from vertical to horizontal position, activating water flow. While unit is in operation, waste water is collected in drain pan and re-directed to daylight drain for drainage out the front of unit. Unit remains in operation until cover is returned to closed position.
Eye/Face Wash Spray Head Assembly: Two FS-Plus™ spray heads mounted on supply arms. Each spray head has individually adjustable flow control and filter to remove impurities from water flow.
Eye/Face Wash Valve: 1/2″ IPS brass plug-type valve with O-ring seals. Furnished with in-line strainer to protect valve from debris and foreign matter.
Mounting: 16 gauge stainless steel cabinet with flange featuring 3/8″ return for recessed mounting in wall. Unit fits in standard 3-5/8″ deep wall.
Pipe And Fittings: Exposed pipe and escutcheon are brushed stainless steel.
Supply: 1″ NPT female inlet.
Waste: 1″ IPS stainless steel drain elbow on front of unit.
Sign: ANSI-compliant identification sign.
Quality Assurance: Unit is completely assembled and water tested prior to shipment.

Application: EyeSafe™ faucet-mounted eyewashes convert any faucet into an emergency eyewash station without interfering with normal faucet operation. An EyeSafe™ unit may be installed at any sink, close to where accidents might occur. In an emergency, the unit is quickly located and activated, and provides an unlimited supply of potable water for rinsing the user’s eyes.
Operation: Unlike conventional faucet-mounted eyewashes, the G1201 offers the ability to activate the eyewash in a single motion. The unit is equipped with a diverter valve for the eyewash and a separate control valve for the faucet. Once the unit is installed on a faucet, the faucet may be opened and left “on” to a preset temperature. To use the faucet, the flow of water is controlled by a quarter-turn ball valve and knob at the bottom of the eyewash. To use the eyewash, simply pull the knob on the front of the eyewash. Since the faucet is open, this is the only step required to activate the eyewash. Water pressure holds the eyewash in operation, leaving the user’s hands free, To return to normal faucet operation, push the knob in or turn off the faucet.
Outlet Heads: Outlet heads are mounted 5″ apart and deliver a soft, aerated flow of water. Heads angle forward and inward toward user. Angle of heads is adjustable to permit full coverage and avoid splashing. Furnished with float-off dust covers to protect outlet heads.
Eyewash Valve: Forged brass diverter valve.
Faucet Control Valve: Quarter turn ball valve with chrome plated brass ball, molded TFE seals and plastic handle.
Inlet: Body has 55/64″-27 female thread. Furnished with three adaptors (15/16″-27, 13/16″-27 and 3/8″ IPS) for installing on most commonly used faucets, including laboratory-type faucets.
Outlet: Furnished with removable aerator on bottom.
Quality Assurance: Each unit is completely assembled and water tested prior to shipment.
Important: Faucet-mounted eyewashes, whether manufactured by Guardian Equipment or other companies, require two motions to operate (turn on water, pull knob to activate eyewash flow). Therefore, Guardian does not believe that these units meet the provisions of ANSI Z358.1-2014 as eyewash units. These units are intended solely as supplemental units in addition to dedicated, plumbed eyewash equipment installed in the workplace.
Faucet-mounted eyewashes should be used with cold or warm water only. Use of hot water might cause scalding.

Application: EyeSafe™ faucet-mounted eyewashes convert any faucet into an emergency eyewash station without interfering with normal faucet operation. An EyeSafe™ unit can be installed at any sink, close to where accidents might occur. In an emergency, the unit is quickly located and activated, and provides an unlimited supply of potable water for rinsing the user’s eyes. Faucet control valve offers single motion eyewash activation by allowing the pull knob to control water flow while the faucet remains ‘on’ at a preset temperature.
Operation: Unlike conventional faucet-mounted eyewashes, the G1200 offers the ability to activate the eyewash in a single motion. The unit is equipped with a diverter valve for the eyewash and a separate control valve for the faucet. Once the unit is installed on a faucet, the faucet may be opened and left “on” to a preset temperature. To use the faucet, the flow of water is controlled by a quarter-turn ball valve and knob at the bottom of the eyewash. To use the eyewash, simply pull the knob on the front of the eyewash. Since the faucet is open, this is the only step required to activate the eyewash. Water pressure holds the eyewash in operation, leaving the user’s hands free. To return to normal faucet operation, push the knob in or turn off the faucet.
Outlet Heads: Outlet heads are mounted 3″ apart and deliver a soft, aerated flow of water. Heads angle forward toward user. Angle of heads is adjustable to permit full coverage and avoid splashing. Furnished with float-off dust covers to protect outlet heads.
Eyewash Valve: Forged brass diverter valve.
Faucet Control Valve: Quarter turn ball valve with chrome plated brass ball, molded PTFE seals and plastic handle.
Inlet: Body has 55/64″-27 female thread. Furnished with three adaptors (15/16″-27, 13/16″-27 and 3/8″ NPS) for installing on most commonly used faucets, including laboratory-type faucets.
Outlet: Furnished with removable aerator on bottom.
Quality Assurance: Each unit is completely assembled and water tested prior to shipment.
Important: Faucet-mounted eyewashes are intended solely as supplemental units in addition to dedicated, plumbed eyewash equipment installed in the workplace.
Faucet-mounted eyewashes should be used with cold or warm water only. Use of hot water might cause scalding.
Leaving a faucet “on” with a valve at the outlet closed can cause cross-mixing of the hot and cold water. The water supply lines or the faucet should be furnished with check valves to prevent such mixing from occurring. This unit should not be installed on a faucet with an atmospheric vacuum breaker, as the faucet control valve downstream of the vacuum breaker will interfere with its function. Guardian Equipment recommends consulting with local plumbing code authorities prior to installing this unit.


Cover, EQUIPMENT G1540CVR G1540CVR, SKU: G0657091 Product Details Flange, Features In.
Mounting With and Drench About Us small business stay competitive! We offering of products low prices. historically been at disadvantage who at of their size. want change Zoro has the “big we offer one There are discount structures to understand.
Every the same an you to or one We have our headquarters in Grove, petitioning town rename (We’re Buffaloes.) Like believe that always put our customers first.

Application: Free standing, pedestal mounted eye/face wash. Two large FS-Plus™ spray-type outlet heads deliver a flood of water for rinsing eyes and face.
Spray Head Assembly: Two FS-Plus™ spray heads. Each head has a “flip top” dust cover, internal flow control and filter to remove impurities from the water flow.
Valve: 1/2″ IPS chrome plated brass stay-open ball valve. Valve is US-made with chrome plated brass ball and PTFE seals.
Bowl: 11-1/8″ diameter stainless steel.
Pipe And Fittings: Schedule 40 galvanized steel. Furnished with orange polyethylene pipe covers for high visibility and corrosion resistance.
Supply: 1/2″ NPT female inlet.
Waste: 1-1/4″ NPT female outlet.
Sign: ANSI-compliant identification sign.
Quality Assurance: Valve, bowl and spray head assembly is factory assembled and water tested prior to shipment.